专利摘要:
The scope of the invention is to make a more simple construction of the current transducer currently used widely in circuit breakers for application within the scope of low voltage directive. The invention removes the energy coil from the current transducer and adds additional features and requirements to control circuit in order to keep the protective functionality of an automatic circuit breaker. The benetit of the solution is a highly improved performance with respect to harmonics and higher frequency in the low voltage grid. The higher performance will in addition yield a higher rel iability when the circuit breaker is mounted into a grid environment with high frequency pollution.
公开号:DK201400213A1
申请号:DK201400213
申请日:2014-04-14
公开日:2015-11-02
发明作者:John Larsen
申请人:Siemens Aktieselskab;
IPC主号:
专利说明:

intrisduiClioo [0001] The invention relates to current transformer or current transducer fCT) used in Automatic Circuit breakers at low voltage in accordance to the low voltage directive, 1ECS043S. The current transformers are used for measuring of the current in the main paths Li, L2 and 13 as well as delivering energy to the trip unit implemented in the automatic circuit breaker. [0002] The circuit breakers in scope for this invention are automatic circuit breakers that are certified in accordance with the low voltage directive IEG80439 with one or more poles. Besides that the circuit breaker can be of any kind of Vacuum breakers, Air Circuit Breakers. Molded Case Circuit Breakers, Miniature Circuit Breakers and Load breakers. [0003] It' well known to use the current transformers (CTs) in circuit breakers, but up until now these CTs have for the main paths Of current L1. L2 and 13 been implemented with two independent coils. 1. Rogowski coil or haii element for measuring of currents in the main current path L1,12, L3, N, RE 2. Energy coii for generating energy to the trip unit. The energy is transformed via the three main phases, LI. 12, and L3. [0004] As the CTs are designed to operate at the natural frequency of the circuit in which they are implemented, the CTs are vulnerable and weak against higher frequencies including harmonics, The typical natural frequency of the grid network could be 50Hz/SOHs/200Rz/4GOHz, but can in general of any kind of frequency .
[0005] The presence of harmonics are getting more and more typical in numerous applications involving converters, motor drives, switched power supplies etc. in ail switched power networks the issues with higher frequencies disturbances and harmonics will be more and more significant.
[0008] As the purpose of the energy-transformer is to deliver energy at the natural frequency, the performance is optimised for this frequency. This approach have the side affect that higher frequencies will cause higher loses in the energy transformer, which wili be transferred to heat loses
[0007] It’s the scope of this invention to simplify the CT by removing the energy transformer for improved performance against higher frequencies generated by switching devices in the gnd, but stiii keep the functionality and protection capabilities of an automatic circuit breaker.
Detailed description
[0008] In applications using switched network in low voltage power circuits the voltage and current wili always be affected by the switching in the low voltage power circuit
[0009] The switching of the power circuits are typically performed by switching the three phases LI, L2 and L3 using a PWM signal in order to meet a specific power level. The switching frequency is depended on application and / or power level required.
[0010] The principal in the switching device is to switch the main phases L1, L2 and L3 at a higher frequency than the natural frequency of the grid The switching frequency can in principal fee of any frequencies between 0 Hz ~ infinity. [0011] it’s inevitable that the switching will affect the THD (Totai Harmonics Distortion) level of the power delivered from the switching circuit The voltage / current waveform hence wiii consist of two frequency components: 1:, The natural frequency of the grid in which the switch device operates and I; The switching frequency and all the harmonics related to the natural frequency and the switching frequency. [0012] The presence of higher frequencies than the natural frequency of the network wilf affect the performance of the components used In the network, as these are typical designed for usage at the natural frequency of the network. [0013] For Circuit Breakers, which can be of any kind of Vacuum breakers, Air Circuit Breakers, Molded Case Circuit Breakers, Miniature Circuit Breakers, Load breakers the currents are typically measured by the usage of a CT (Current Transducer or Current Transformer). [0014] The CT for the circuit breakers consists of several parts. The housing for the components [1] is typically made of a type of molded plastic. The inside of the housing [1] can either by free air or filled with mold material. The Rcgowski current transformer [2] transforms the main current from the busbar [7] with any kind of scaling to a measuring current for the trip unit through the cables [6], The energy transformer [3] consists of a primary winding, which is coupled around the main current busbar [ ], the core [3] * |4| for improving flux density at the natural frequency at low voltage Ex, S0Hz/6OHs/2OOHz/4OOHz: The secondary winding is connected to the trip unit through cables [5] for energy supply to the electronic trip unit. The energy transformer [3] and the core [3] * [4] are designed for the usage at the natural frequency of the network In which the circuit breaker is mounted Ex. 6OHz/6OHz/2O0HaMQ0Hz.
[00 55] As the purpose of the energy transformer is to deliver energy at the natural frequency, the performance is optimized for this frequency. This approach have the side affect that higher frequencies will causes higher loses in the energy transformer, which will be: transferred to heat loses,
[0016] The invention wiii remove the energy transformer [3] + [4], as these are the parts which causes the increased heat loses. The Trip Unit [12] can be either self powered with energy from the energy transformer or powered using an external power supply.
[0017] The invention will be based on the solution of using an external power supply and not support the usage of the self powered application,
[0018] In order to make sure that the protection functionality of the circuit breaker is Intact at a power failure of the external power supply for die Trip Unit: [12], the invention make use of th ree different solutions for power and/or voltage monitoring of the power supply for the Trip Unit, 1, The Trip Unit [12] has a dedicated internal sensor circuitry for monitoring the power supply.
2, The circuit breaker have two UVR (Under Voltage Release) [13] + [14] implemented, where one of these are dedicated for monitoring of the power supply for the Trip Unit 3. An external relay or contactor is incorporated in the external control circuitry for the circuit breaker. The external relay or contactor [18] is wired to the power supply for the Trip Unit [12], 4 An externa! voltage monitoring device [17] and/or current monitoring device [18} is incorporated In the externa! control circuitry for the circuit breaker. The externa! monitoring device is wired to the power supply for the Trip Unit [12], [0019] Description of case 1, The internal circuitry for monitoring of the auxiliary power supply for the Trip Unit [12] is either coupled to the tripping coil [15j independently or connected together with the tnp signals implemented in the Trip Unit. In ali cases the monitoring circuitry trips the circuit breaker in case the supply is below the range of proper operation of the Trip Unit [12], The monitoring of the auxiliary supply can be of voltage, current or power consumption. The monitoring circuitry sends a signal to the tripping coii [15], which makes the circuit breaker trip in case of an undervoltage and/or undercurrent and/or low power consumption of the auxiliary power supply for the Trip Unit. [0020] Description of case 2. The tripping of the circuit breaker in case of failure at the auxiliary power supply for the Trip Unit is in this case realized by using a UVR [13] * [14], if the circuit breaker is only mounted with one UVR, the UVR [13] should be wired to the power supply lines [8] for Trip Unit [12f. The limitation is m this case that the UVR [13] needs to operate in the same voitage rating as the Trip Unit. To overcome this, a second UVR [14] couid be used, if the circuit breaker is implemented with two UVR's [13J + [14], one UVR [13] could be rated for the same voitage rating as the voitage rating for the Trip Unit [12], and wired to the power supply fines [8] + [10] for the Trip Unit The other UVR [14] could be used at any voltage ratings available for the UVR.
[0021] Description of case 3. The tripping of the circuit breaker in case of failure at the auxiliary power supply [10] is In this case by using an external relay or contactor [15] in combination with an UVR [14], lithe circuit breaker is only mounted with one UVR [14], and the application requires an UVR with a different voitage rating than the Trip Unit [12] the usage of an externa! reiay or contactor [18] is needed. The coii of the externa! reiay or contactor [16] is wired to the auxiliary power supply line [10] for the Trip Unit [1:2], For the purpose of tripping in case of undervoltage at the auxiliary supply, it doesn't matter whether the obi! is wired to the positive or the negative pole for the power supply [10], In case of an undervoltage at the auxiliary supply, the coil connected to the auxiliary supply will be de-energized and the contact set of the externa! relay or contactor [18] wÉ open, which wiif de-energise the UVR [14] and trip the breaker.
[0022] Description of case 4. The topping of the circuit breakers in case of failure at the auxiliary power supply [10] Is in this case done by externa! monitoring of the auxiliary power supply. The monitoring can either be done by usage of a voltage monitoring device [17] and/or a current monitoring device [18]. in case of an undervoiiage of the auxiliary power supply for the Tnp Unit [10]. the voltage monitoring device opens the contact set of the voltage monitoring device [1 ], which will de-energize the UVR [14] and trip the breaker, in case of an undervoitage of the auxiliary power supply for the Trip Unit [10], the current monitoring device opens the contact set of the current monitoring device [17], as the current flow will lower than expected: which Is set to a threshold value. The open contacts set will deenergize the UVR [141 and trip the breaker. [0023] The above mentioned four options can either be implemented as stand-alone options, or one or more options can be implemented at once. Regardless of how many options are implemented at once the invention will ensure that the protection functionality of the breaker is Intact, and therefore the circuit breaker can he categorized as either switch disconnector., which is a non-automatic breaker or categorized as an automatic circuit breaker. [0024] The enhancement of removing the energy transformer from the CT will be significantly increase in performance for harmonics performance in switched network compared to the traditional CT with both energy and Rogowski transducer. The increased performance is obtained be removing the lossy part of the combined current transformer.
权利要求:
Claims (6)
[1] 2. Circuit breaker according to claim | compromising of at least one Current Transducer that is characterized by only containing a transducer for measuring the current in the main path.
[2] 3. Circuit breaker according to claim1 and 2 compromising of a Trip Unit that is characterized by only using an externa! auxiliary power suppiy.
[3] 4. Circuit breaker according to previous claims compromising of at least one UVRihaf is charaeterizedby energizing the trip coil in the circuit breaker in case of an underyoitage.
[4] 5. Circuit breaker according to previous claims that is characterized by the capability to monitor the auxiliary suppiy voltage.
[5] 6. Circuit breaker according ίο previous claims that is characterized by using an external relay and/or contactor for disconnection of power supply io the UVR,
[6] 7. Circuit breaker according to previous claims that is characterized fey using an external voltage monitor unit for disconnection of power suppiy to the UVR
类似技术:
公开号 | 公开日 | 专利标题
KR101451387B1|2014-10-22|The Switchboard with the device of sensing open state of the secondary terminal and protecting of a current transformer
US20130070374A1|2013-03-21|Electrical monitoring device and method for safeguarding the protective function of a type a residual current device |
US20150333509A1|2015-11-19|Protective Circuit for a Current Transformer and Current Transformer with a Protection Circuit
US10014679B2|2018-07-03|Electrical switching apparatus including alternating current electronic trip circuit with arc fault detection circuit and power supply
CN102386024B|2015-01-14|Power supply for an electronic tripping unit for a switch, in particular a circuit breaker for low voltages, and a switch having a power supply such as this
DK201400213A1|2015-11-02|Current Transducer without energy coil for circuit breakers
US9384928B2|2016-07-05|Electrical switching apparatus including transductor circuit and alternating current electronic trip circuit
CN203761036U|2014-08-06|Line protection device
RU145143U1|2014-09-10|RECEIVING DISTRIBUTION DEVICE FOR ELECTRIC NETWORK FOR SINGLE-PHASE NETWORK
EP2509092B1|2015-08-05|Electric switching device
CN202564798U|2012-11-28|Intelligent harmonic and arc extinction switch cabinet
Fidigatti et al.2010|Effect of harmonic pollution on low voltage overcurrent protection
CN203747286U|2014-07-30|Permanent-magnet high-voltage switch measurement integrated device
Biasse et al.2009|Circuit-breaker RMU improves MV/LV transformer protection
US9025298B2|2015-05-05|Electrical switching apparatus including transductor circuit and alternating current electronic trip circuit
SI24088B|2017-07-31|Electric circuit overload protecting device and with integrated electricity consumption meter
KR101432452B1|2014-09-23|Switchgear including multi-feeder protection relay
CN203135434U|2013-08-14|Neutral point virtual grounding device
Han et al.2011|Study on protection scheme for traction transformer of high-speed railway
CN201069700Y|2008-06-04|High-stability dry three-phase combined mutual inductor
CN102386025B|2015-07-15|Switch, in particular circuit breaker for low voltage, and power supply for an electronic trip unit of a switch
Hiroshi2012|Interruption technology of breakers for high-voltage direct current
CN205724836U|2016-11-23|A kind of leakage overload protector
CN203434448U|2014-02-12|Combined breaker of reclosing controller
CN204204620U|2015-03-11|The outdoor integrated strip zero-sequenceprotection current transformer of pvs |
同族专利:
公开号 | 公开日
DK178815B1|2017-02-13|
引用文献:
公开号 | 申请日 | 公开日 | 申请人 | 专利标题
JPH05342969A|1992-06-12|1993-12-24|Toshiba Corp|Circuit breaker|
EP1098415A2|1999-11-05|2001-05-09|Siemens Energy & Automation, Inc.|A circuit breaker system with ASM instantaneous overcurrent indication|
WO2006023811A1|2004-08-20|2006-03-02|Cooper Technologies Company|Removing an automatic circuit recloser from service prior to battery failure|
US8587149B2|2008-01-14|2013-11-19|Abb S.P.A.|Electronic protection unit for automatic circuit breakers and relative process|
US20100079923A1|2008-09-30|2010-04-01|General Electric Company|Multi-function circuit interruption accessory|
US20100123991A1|2008-11-14|2010-05-20|Square D Company|Backup tripping function for a circuit breaker with microcontroller-based fault detection|
EP2690643A1|2012-07-24|2014-01-29|ABB S.p.A.|An improved solid state switching device.|
法律状态:
2018-11-14| PBP| Patent lapsed|Effective date: 20180414 |
优先权:
申请号 | 申请日 | 专利标题
DK201400213|2014-04-14|
DKPA201400213A|DK178815B1|2014-04-14|2014-04-14|Power Transducer without Power Circuit for Circuit Breakers|DKPA201400213A| DK178815B1|2014-04-14|2014-04-14|Power Transducer without Power Circuit for Circuit Breakers|
[返回顶部]